SM 231 - Analog input ECO
4x AI
12 Bit
Current 4...20 mA, +/-20 mA
Parameterizable
SM 231, ECO (231-1BD40)
SM 231, ECO (231-1BD40)
Technische Daten
Bestellnummer: 231-1BD40
Typ: SM 231, ECO
Allgemeine Informationen:
- Hinweis: -
- Merkmale: 4x AI, 12 Bit, Strom 4...20 mA, +/-20 mA, parametrierbar
Stromverbrauch/Leistungsverlust:
- Stromverbrauch vom Backplane-Bus: 120 mA
- Leistungsverlust: 0,6 W
SM 231, ECO (231-1BD40)
Technical Data
Order no.: 231-1BD40
Type: SM 231, ECO
General Information:
- Note: -
- Features: 4x AI, 12 Bit, Current 4...20 mA, +/-20 mA, Parameterizable
Current Consumption/Power Loss:
- Current consumption from backplane bus: 120 mA
- Power loss: 0.6 W
Technical Data Analog Inputs:
- Number of inputs: 4
- Cable length, shielded: 200 m
- Rated load voltage: -
- Current consumption from load voltage L+ (without load): -
- Voltage inputs: -
- Min. input resistance (voltage range): -
- Input voltage ranges: -
- Operational limit of voltage ranges: -
- Operational limit of voltage ranges with SFU: -
- Basic error limit voltage ranges: -
- Basic error limit voltage ranges with SFU: -
- Destruction limit voltage: -
- Current inputs: yes
- Max. input resistance (current range): 110 Ohm
- Input current ranges: -20 mA ... +20 mA, +4 mA ... +20 mA
- Operational limit of current ranges: +/-0.2% ... +/-0.5%
- Operational limit of current ranges with SFU: -
- Basic error limit current ranges: +/-0.1% ... +/-0.2%
- Radical error limit current ranges with SFU: -
- Destruction limit current inputs (electrical current): max. 40 mA
- Destruction limit current inputs (voltage): -
- Resistance inputs: -
- Resistance ranges: -
- Operational limit of resistor ranges: -
- Operational limit of resistor ranges with SFU: -
- Basic error limit: -
- Basic error limit with SFU: -
- Destruction limit resistance inputs: -
- Resistance thermometer inputs: -
- Resistance thermometer ranges: -
- Operational limit of resistance thermometer ranges: -
Status Information, Alarms, Diagnostics:
- Status display: none
- Interrupts: no
- Process alarm: no
- Diagnostic interrupt: no
- Diagnostic functions: no
- Diagnostics information read-out: none
- Supply voltage display: none
- Group error display: red SF LED
- Channel error display: none
Isolation:
- Between channels: -
- Between channels of groups: -
- Between channels and backplane bus: yes
- Between channels and power supply: -
- Max. potential difference between circuits: -
- Max. potential difference between inputs (Ucm): -
- Max. potential difference between Mana and Mintern (Uiso): -
- Max. potential difference between inputs and Mana (Ucm): -
- Max. potential difference between inputs and Mintern (Uiso): -
- Max. potential difference between Mintern and outputs: -
- Insulation tested with: DC 500 V
Datasizes:
- Input bytes: 8
- Output bytes: 0
- Parameter bytes: 12
- Diagnostic bytes: 0
Housing:
- Material: PPE / PA 6.6
- Mounting: Profile rail 35 mm
Mechanical Data:
- Dimensions (WxHxD): 25.4 mm x 76 mm x 88 mm
- Net weight: 90 g
- Weight including accessories: -
- Gross weight: -
Environmental Conditions:
- Operating temperature: 0 °C to 60 °C
- Storage temperature: -25 °C to 70 °C
Certifications:
- UL certification: yes
- KC certification: -